Pheasants International provides HEPA filter integrity testing in Pakistan for pharmaceutical manufacturing, hospitals, laboratories and controlled environments.
A HEPA filter integrity test introduces an aerosol challenge upstream of the installed filter and scans the downstream face, frame and gasket with a photometer probe to detect leaks that particle counting alone will not find.
A particle count tells you the room is clean at that moment. An integrity test tells you whether the filter, its seal and its housing are actually intact — which is what a regulator asks about at requalification.

Contact US

Benefits

  • Leaks found that particle counting misses — medium pinholes, gasket bypass, frame seal failure
  • Requalification passed with evidence — scan data recorded per filter, not per room
  • Product protection assured — filter integrity is the barrier between process and contamination
  • Filters replaced only when necessary — repairable leaks identified within permitted limits
  • Audit-ready documentation — formatted for IQ/OQ/PQ inclusion
  • Full cleanroom certification available in a single visit
  • Scheduled around production windows

How we work

Review

Filter schedule, room classification, protocol and acceptance criteria

Verify

Airflow and system stability confirmed before challenge

Challenge

PAO aerosol introduced upstream and concentration measured

Scan

Downstream face, frame and gasket scanned at controlled traverse rate

Assess

Leaks quantified against the acceptance threshold

Remediate

Per-filter results, scan data, instrument calibration, certification status

Report

Leakage rate, class achieved, pass or fail and marked-up drawings

  • HEPA filter integrity testing
  • ULPA filter integrity testing
  • PAO and DOP aerosol challenge testing
  • Filter housing and gasket seal testing
  • Airflow velocity and uniformity measurement
  • Air change rate verification
  • Room pressure cascade testing
  • Non-viable particle counting and ISO classification
  • Recovery testing
  • Airflow visualization and smoke pattern studies
  • Laminar flow unit and biosafety cabinet testing
  • Cleanroom certification and requalification
  •  ISO 14644-1 ·
  • ISO 14644-3
  • · EU GMP Annex 1
  • · IEST recommended practices
  • Pharmaceutical manufacturing

  • Hospitals and operating theatres

  • Compounding pharmacies

  • Medical device production

  • Biotechnology laboratories

  • Electronics and semiconductor assembly

  • Food and beverage processing

  • Research facilities

  • Scan data recorded per filter, giving traceable evidence at requalification
  • Testing at rest and in operation as your protocol requires
  • Repair-and-rescan approach — filters replaced only when the leak exceeds permitted limits
  • Complete cleanroom scope — integrity testing, particle counts, pressure cascade and recovery together
  • Documentation formatted for GMP audit and validation file inclusion
  • Established HEPA supply and testing presence in Pakistan

Frequently Asked Questions

What is a HEPA filter integrity test?

A HEPA filter integrity test introduces an aerosol challenge upstream of an installed filter and scans the downstream face, frame and gasket with a photometer to detect leaks. It verifies the filter, its seal and its housing are intact, which particle counting alone cannot confirm.

Which company provides HEPA filter integrity testing in Pakistan?

Pheasants International provides HEPA filter integrity testing and cleanroom certification across Pakistan to ISO 14644-3 procedures for pharmaceutical, healthcare and laboratory facilities.

What is the HEPA filter integrity test frequency?

Typically every six to twelve months depending on room classification and your validation protocol, and always after filter replacement or any work affecting the ceiling grid or filter housing.

What is the difference between an integrity test and a particle count?

A particle count measures airborne particle concentration in the room at that moment. An integrity test verifies the filter and its seal are physically intact. Regulators generally expect both, because a room can pass a particle count with a leaking filter.

What aerosol is used for HEPA integrity testing?

PAO is the most widely used challenge aerosol, with DOP used in some protocols. The aerosol is introduced upstream at a measured concentration and detected downstream by photometer.

What happens if a HEPA filter fails the integrity test?

Leaks within the limits permitted by the protocol may be repaired and the filter rescanned. Leaks beyond those limits require replacement and retesting. Both results are recorded in the report.