Pheasants International provides staircase pressurization testing services in Pakistan for high-rise commercial, residential, hospital and hotel projects.
Staircase pressurization testing verifies that a pressurized staircase maintains the required pressure differential across stair doors during a fire while still allowing occupants to open those doors.
A pressurized stairwell only saves lives if it works under real fire conditions. Systems fail in two opposite directions, and both are invisible until measured. Either pressure collapses when doors open, letting smoke into the escape route — or pressure builds so high that occupants physically cannot pull the door open.

Contact US

Benefits

  • Both failure modes tested — pressure loss and over-pressurization
  • Occupant egress proven — door opening force measured at every level, not calculated
  • Completion approval supported — documented evidence for the authority having jurisdiction
  • Every floor tested, not a sample — differentials vary significantly up a tall building
  • Criteria confirmed against your fire strategy — not assumed from a generic figure
  • Latent faults surfaced — dampers, relief controls and fan capacity checked under load
  • Life safety demonstrated, not presumed

How we work

Review

Approved fire strategy, design criteria, sequence of operation, code edition

Verify readiness

Fan installation, dampers, relief controls, alarm interface

Test closed-door condition

Differential pressure at every stair door on every floor

Test open-door condition

Repeat with the design number of doors held open

Measure door force

Calibrated push-pull gauge at each level

Test alarm response

Fan start, response time, standby power changeover

Report

Results against code criteria, with failures and their likely cause

  • Differential pressure measurement across every stair door
  • Pressure retention verification with design doors open
  • Door opening force measurement using a calibrated force gauge
  • Air velocity measurement through open doorways
  • Pressurization fan airflow, static pressure and motor readings
  • Relief damper and over-pressure control verification
  • Staircase pressurization calculation review against measured results
  • Fan response time from fire alarm signal
  • Standby power changeover verification
  • Lift lobby, refuge area and corridor pressurization
  • Certified report against project fire strategy
  •  NFPA 92 ·
  • NFPA 101
  • IBC Section 909
  • High-rise residential towers

  • Commercial office towers

  • Hotels

  • Hospitals

  • Shopping malls

  • Mixed-use developments

  • Government and

  • institutional buildings

  • Airports

  • Calibrated force gauge used — an improvised tool is not acceptable documentation
  • Tested to your approved fire strategy, since criteria vary by code edition and sprinkler status
  • Every floor measured — differentials change with height through stack effect
  • Failure cause identified — damper, fan, relief control or leakage
  • Coordinated with fire alarm testing where sequence verification is required
  • We also design these systems, so the fix comes with the finding

Frequently Asked Questions

What is staircase pressurization testing?

Staircase pressurization testing verifies that a stairwell pressurization system maintains the required pressure differential across stair doors during a fire while still allowing occupants to open those doors, measuring differential pressure, door opening force and airflow through open doorways.

Which company provides staircase pressurisation testing in Pakistan?

Pheasants International provides pressurized staircase testing across Pakistan for high-rise commercial, residential, hospital and hotel projects, testing to NFPA 92 and NFPA 101 with certified documentation.

Why won't my stairwell fire door open?

Over-pressurization. The fan delivers more air than the stairwell can relieve, so pressure across the door exceeds what a person can overcome. NFPA 101 limits door opening force to 30 lbf (133 N), and relief damper faults are the usual cause.

Why do stairwell pressurization systems fail?

Common causes are dampers not fully closing or leaking past their seats, degraded fan capacity from worn belts or dirty filters, relief dampers stuck, duct leakage developed since installation, and stack effect in tall buildings.

Does a staircase pressurization calculation replace testing?

No. The calculation establishes the design intent. Testing verifies whether the installed system achieves it, and installed systems routinely differ from calculated performance because of leakage, damper faults and construction variation.

How often should stair pressurization systems be tested?

At commissioning, then periodically as required by the authority having jurisdiction and your fire strategy. Retesting is advisable after any modification to the stairwell, HVAC system or fire alarm.